Features: · EIB Bus Interface Module for piggyback-use on PCBs· MC68HC05B6 with mask programmed ROM, contains the EIB System Software· PEI *) and Port A, PLM A and PLM B for applications available· Smallest instabus EIB Bus Access Unit· Operating Temperature Range: BIM M111: - 5 to + 45 °C BIM M11...
5WG1118AA01: Features: · EIB Bus Interface Module for piggyback-use on PCBs· MC68HC05B6 with mask programmed ROM, contains the EIB System Software· PEI *) and Port A, PLM A and PLM B for applications available· ...
SeekIC Buyer Protection PLUS - newly updated for 2013!
268 Transactions
All payment methods are secure and covered by SeekIC Buyer Protection PLUS.
To avoid malfunctioning by EMI, it is recommended to shield the BIM. The connection for the electric screen is shown in the figure below.
The data contained herein are subject to change without notice. Siemens does not warrant for correctness or completeness of the documentation or that the products described are
qualified for certification.
Rating | Symbol | Value | Units |
Bus Voltage | V Bus | ± 35 | V |
Microcontroller Input Voltage PEI, PLMA, PLMB, Reset, LED, Button |
V... | GND - 0,5 to Vcc + 0,5 | V |
Microcontroller input or output current per Pin |
I | see Motorola Technical Data MC68HC05B6 |
The BIM M111 or the BIM M115 are members of Siemens instabus EIB BCU - family. They areespecially designed as small modules for piggyback use and can be fitted directly into PCBs. The BIM M111 or the BIM M115 contain all functional parts of a EIB - BCU with the exception of shift register for the serial synchronous interface. Additionally access to such microcontroller ports as Reset, PLMA, or Port A is possible. These ports are directly accessible by the user. Additional pins for the connection of an external programming button and a LED are available. For applications with the need of longer 'Bus Buffer Time' the BIM M111 or the BIM M115 allows to connect an additional capacitance at bus voltage level.