PM-Hx22 Maximum Ratings
Output 0-5Vdc (self powered)
Frequency 50/60Hz
Insulation class 600Vac RMS
Accuracy ±2% of full scale
Response time 2 seconds
Ambient:
Temperature -15 to 60°C
Humidity 0 to 95% non-condensing
Sensing aperture:
Solid core 19mm dia.
Split core 28 x 23mm (self gripping iris)
Dimensions:
Sold core 74H x 76W x 27D mm
Split core 74H x 65W x 26D mm
Protection IP20
Country of origin U.S.A
PM-Hx22 Features
• 3 Selectable ranges
• Load trending
• Motor control
• For use inside a separate fire or electrical enclosure
• For use in a Measurement category III environment, or less, as per IEC 61010-1:2001