relay-H550

Features: Suitable for indicating a ground fault condition on a generator set which is either locally or remotely grounded.Power - Operates on 24 VDC (nominal) control power - fully functional at voltages from 18-30 VDC.Direct connection - Suitable for direct connection to generator sets operating...

product image

relay-H550 Picture
SeekIC No. : 004476060 Detail

relay-H550: Features: Suitable for indicating a ground fault condition on a generator set which is either locally or remotely grounded.Power - Operates on 24 VDC (nominal) control power - fully functional at vo...

floor Price/Ceiling Price

Part Number:
relay-H550
Supply Ability:
5000

Price Break

  • Qty
  • 1~5000
  • Unit Price
  • Negotiable
  • Processing time
  • 15 Days
Total Cost: $ 0.00

SeekIC Buyer Protection PLUS - newly updated for 2013!

  • Escrow Protection.
  • Guaranteed refunds.
  • Secure payments.
  • Learn more >>

Month Sales

268 Transactions

Rating

evaluate  (4.8 stars)

Upload time: 2024/4/24

Payment Methods

All payment methods are secure and covered by SeekIC Buyer Protection PLUS.

Notice: When you place an order, your payment is made to SeekIC and not to your seller. SeekIC only pays the seller after confirming you have received your order. We will also never share your payment details with your seller.
Product Details

Description



Features:

Suitable for indicating a ground fault condition on a generator set which is either locally or remotely grounded.

Power - Operates on 24 VDC (nominal) control power - fully functional at voltages from 18-30 VDC.

Direct connection - Suitable for direct connection to generator sets operating at voltages up to 600 VAC (line to line).
 
Ground fault current settings - 100-1200 A, in 10 discrete settings: 100, 150, 200, 250, 300, 450, 600, 750, 800, 1200 A.

Monitoring - Provides continuous monitoring of neutral-to-ground with LED indication for open connection.

Factory mounted controls - Available factorymounted and interconnected to Cummins Power Generation Detector™ series PowerCommand® controls.

Link reconnection - For use with either 3-pole (solid neutral or 4-pole (switched neutral) transfer switches.

Indicating lamps - For Relay on (green), ground fault current over setting (red), loss of ground connection (red).

Time delay settings - 0-1.0 seconds.

Circuit board - One-piece molded case fully potted.

Contacts - One set of form C output, rated 1100 VA, 250 VAC, 5 A continuous, 3 A breaking @ 240 VAC.

"Test" - Push-button.

"Reset" - Push-button.

Percent full scale metering output - 0-1 mA full scale.

Bonding jumper - Sized per NEC requirements.



Description

NFPA 70, the U.S. National Electrical Code (NEC) requires that services of 1000 amps and larger in capacity which operate at more than 150 volts from line-to-neutral must be provided with ground fault equipment. Generator sets of relay-H550 rated at 100 amps and larger which serve as emergency power must be provided with ground fault indication equipment. Health care facilities of relay-H550 that utilize ground fault protection equipment must be provided with a coordinated multi-level ground fault system.

Cummins Power Generation ground fault indication equipment of relay-H550 is designed for use in emergency/standby power systems, for indication of ground fault conditions during generator set operation.




Customers Who Bought This Item Also Bought

Margin,quality,low-cost products with low minimum orders. Secure your online payments with SeekIC Buyer Protection.
Semiconductor Modules
LED Products
Power Supplies - Board Mount
Potentiometers, Variable Resistors
View more